OPTIONS Dual 8 A Form C relays Parallel BCD output, isolated Analog output, isolated and scalable, 4-20 mA, 0-20 mA, 0-10 V 9-32 V isolated DC power Plain front panel without programming keys The P6004 is a special configuration of the six-digit P6000 microprocessor-based rate meter and counter with an isolated analog-to-frequency signal conditioner. The result is a 1/8 DIN software-scalable process meter or integrating totalizer with an exceptionally wide display range, two setpoints and RS-232. Standard input ranges are 4-20 mA, 0-10 V or 0-2 V, with fine zero and span input adjustments at the rear of the meter. PROCESS INDICATOR MODE The analog-to-frequency signal conditioner converts the analog process signal to a frequency from 1 Hz to 10 kHz. In the process indicator mode, this frequency is scaled to engineering units (such as PSI or liters/s) by a six-digit multiplier or divider with any decimal point. An exceptionally wide six digits of zero offset are also available. For instance, this offset can allow the P6004 to display the water level of a canal to 0.1 inch resolution at 1,000 feet above sea level, based on 4-20 mA signal from a pressure transducer at the bottom of the canal and the known altitude of the canal. The display update time can be programmed in 10 ms steps from 50 ms plus one pulse period to 99.99 s. The longer update times provide improved noise rejection by time-averaging the signal. In the process indicator mode, the accuracy of the P6004 is 99.9% at 25°C, as for most 3 1/2 digit meters with dual-slope integration. The temperature coefficient is a low 50 ppm/°C. The number of digits to the right of the decimal point is program-selectable with true roundoff so as to eliminate non-significant digits. INTEGRATING TOTALIZER MODE In the totalizer mode, the 1 Hz to 10 kHz output from the analog-to-frequency signal conditioner is totalized, then scaled to engineering units by a six-digit multiplier or divider with any decimal point. For instance, this allows the P6004 to accept the 4-20 mA signal from a linear flowmeter and display volume in liters or gallons, or to accept the 0-10 V signal from a wattmeter and display kW-hrs. Six digits of preset (display offset) are available, and the P6004 may count up from zero to this preset (positive multiplier or divider) or down from this preset to zero (negative multiplier or divider). In case of a power failure, the latest reading is automatically saved in non-volatile RAM and is restored with power. A low-level cutoff may be jumper-selected to disable totalizing below 0.27% of maximum signal. SIMULTANEOUS RATE AND TOTAL Rate and total can be displayed simultaneously and can each have their own HI and LO setpoints if a basic P6000 is used in combination with a P6004. This is achieved by bringing out the TTL-level 1 Hz to 10 kHz pulses from the analog-to-frequency signal conditioner of the P6004 and using them as input to the basic P6000. LOCAL OR REMOTE PROGRAMMING 1. FRONT-PANEL PROGRAMMING The P6004 can be programmed manually at the front panel, which provides five programming keys and alphanumeric prompting through the LED display. If desired, all setup parameters can be stored in non-volatile RAM. To prevent unauthorized or inadvertent program changes, the P6004 provides four levels of front-panel lockout using push-on jumpers. The front panel can be locked out completely, be locked out except for setpoints, or be fully usable except for fine-calibration of the crystal clock. Saving program changes in non-volatile RAM can also be locked out, so that previously stored setup parameters can always be recalled. Once the program is stored in non-volatile RAM, an optional front panel without keys can be substituted for the standard front panel with keys. The P6004 can also be programmed remotely by down-loading setup parameters from a host computer via RS-232 using direct wiring or a modem. It is well suited for ATE and other computer-controlled applications, since the host computer or programmable controller can dynamically change all setup parameters, including setpoints, and receive data via RS-232. To aid in programming, an IBM PC compatible 5i1/4 inch floppy disk with a menu-driven setup program is available as a low-cost option. DATA, ALARM AND CONTROL OUTPUTS RS-232 and 20 mA serial ASCII communications are standard on the main board, as are three open-collector outputs rated 30 V, 150 mA. The P6004 also offers a choice of three upper-board options: Isolated parallel BCD output allows the P6004 to be interfaced to programmable controllers and to Newport's Model 820A printer. The combination of a P6004 with an 820A constitutes a low-cost datalogging system, where the readings are tagged with time and date. Dual 8 A Form C relays allow the P6004 to switch resistive loads up to 2 kW for alarm and control applications. Isolated analog output provides jumper selection of 0-10 V or 4-20 mA and adjustable zero and span. The 0-10 V output is ideal to drive a stripchart recorder. The 4-20 mA output effectively turns the P6004 into an isolated transmitter. SPECIFICATIONS ANALOG INPUT
Output to main meter: 1 Hz to 10 kHz Low-level shutoff: Jumper selection to disable output below 27 Hz (0.27% of full scale) Zero adjust: ±5% of full scale via potentiometer Span adjust: 6-digit software multiply or divide, any decimal point ISOLATION & NOISE REJECTION CMV, SIG GND to PWR GND or DIG GND: 1500 Vp per HV test, 354 Vp per IEC spacing CMR, SIG GND to PWR GND or DIG GND: 100 dB NMR, SIG HI to SIG LO: 32 dB, 50/60 Hz (in process meter mode at 400 ms update time) ACCURACY AT 25°C Nonlinearity, max: ±0.05% of full scale Accuracy at 25°C: 99.9% of reading Warmup to rated accuracy: 1 hr Response time, min for 10% to 90% for step input: 200 ms Time for display averaging: Programmable, 0 to 99.9 s Tempco, 4-20 mA or 0-10 V: ±0.005%R/°C (50 ppm/°C) Tempco, 0-2 V: ±0.01%R/°C (100 ppm/°C) DISPLAY Type: 7-segment, red LED Digit: 0.56 in (14.2 mm) Symbols: 8.8.8.8.8.8 Display scaling: 6-digit multiply or divide, any decimal point Display offset (or count preset): 6-digits, any decimal point Decimal points: Programmable number of digits to right of decimal point with true roundoff, or 6-digit display with autoranging Display overrange: Exponential notation to 9.99 E9 RS-232 / 20 mA ASCII COMMUNICATIONS (STD) Baud rate: 1200 or 9600 RS-232 voltage levels: +5 V, 6 V RS-232 connections: Data out, data in, RTS, GND 20 mA ASCII connections: Data out, GND Receive capability: Complete program setup Transmit capability: Readings with decimal point, sign, alarm status, unit of measurement, setup data CONTROL, ALARM & DATA OUTPUTS 1. MAIN BOARD (STD) Setpoint output: Three open-collector transistors Power rating: 150 mA sink, 30 V 2. DUAL-RELAY UPPER BOARD (OPT) Output type: Two form-C relays Power rating: 8 A, 30 V dc or 240 V ac, resistive load 3. ISOLATED PARALLEL BCD UPPER BOARD (OPT) BCD type: Isolated, buffered, gated tri-state Digit addressing: 3 or 6 digits at a time Output level: TTL/CMOS, 10 LSTTL loads Power: External 5 V dc for isolated BCD, internal 5 V dc for non-isolated BCD 4. ISOLATED ANALOG OUTPUT UPPER BOARD (OPT) Output level (source): 4-20 mA, 0-20 mA, 0-10 V (jumper-selectable) Compliance for 20 mA source: 12 V Compliance for 10 V source: 20 mA Isolation, SIG GND to ANA GND: 500 Vp Resolution: 1/2048 of output span (11 bits) Accuracy, 10 - 40°C: ±0.1% of theoretical value Step response, 10% to 90% of full-scale: 50 ms Zero and span adjust: Via screwdriver from rear of case Turndown ratio (max zero offset ÷ by min span): 20:1 ENVIRONMENTAL Operating temperature: 0 to 60°C Storage temperature: 40 to +85°C Relative humidity: 95% at 40°C (non-condensing) MECHANICAL Environmental protection: Splash-resistant front panel (std) NEMA-12 lens cover (opt) Dimensions: Newport DIN 4896-150 (1/8 DIN) case, 150 mm behind panel Weight: 21 oz (590 g) Case material: 94V-0 UL-rated polycarbonate ELECTRICAL CONNECTIONS Signal, power, and dual-relay upper-board option: Push-in cable connectors with screw clamping RS232/20 mA ASCII: 10-pin dual-row male header on meter (standard), 10-pin dual-row female cable connector (D10D option) Control I/O functions: 20-pin dual-row male header on meter (standard), 20-pin dual-row female cable connector (D20D option) Parallel BCD upper-board option: 50-pin dual-row male header on meter plus 50-pin dual-row female cable connector (both standard) Note: The male dual-row headers and female cable connectors are per DIN 41612 and provide .100" x .100" (2.54 x 2.54mm) pin spacing. The cable connectors allow mass termination or individual wire connections without solder-ing by using needle-nose pliers or a hand-insertion tool like 3M 3430-01000. HOME / PRODUCT GUIDE / TECHNICAL REFERENCE NEWPORT Electronics, Inc. (714) 540-4914 or Contact Us Copyright 1999, Newport Electronics, Inc. All rights reserved. |